WJ127 General Parameters:
(Typical @+25 ℃, Vs is 24VDC)
Input type: thermocouple signal input, supports multiple thermocouple signals, K/J/T/E/R/S/B/N type thermocouples
Accuracy: 0.1% (excluding cold end sensor error)
Temperature drift: ± 50 ppm/℃ (± 100 ppm/℃, maximum)
Input resistance: greater than 1M Ω
Cold end compensation sensor accuracy: ± 0.5 ℃
Bandwidth:-3 dB 10 Hz
Conversion rate: 10 Sps (factory default value, users can modify the conversion rate by issuing commands.)
You can set the AD conversion rate to 2.5 SPS, 5 SPS, 10 SPS, and 20 SPS by sending commands. (Channel
conversion rate=AD conversion rate/number of open channels)
Note: Please recalibrate the module after modifying the conversion rate, otherwise the measured data may have
deviations. You can also specify the conversion rate when placing an order, and we will
recalibrate the product according to the conversion rate you require when it leaves the factory.
Common moderejection (CMR): 120 dB (1k Ω Source Imbalance @ 50/60 Hz)
Normal mode suppression (NMR): 60 dB (1k Ω Source Imbalance @ 50/60 Hz)
Input protection: overvoltage protection, overcurrent protection
Communication: RS-485 standard character protocol and MODBUS RTU communication protocol
Baud rates (2400, 4800, 9600, 19200, 38400, 57600, 115200bps) can be selected by software
The address (0-255) can be selected by software
Communication response time: 100 ms maximum
Working power supply:+8~32VDC wide power supply range, with internal anti reverse and overvoltage protection
circuits
Power consumption: less than 1W
Working temperature:-45~+80 ℃
Working humidity: 10~90% (no condensation)
Storage temperature:-45~+80 ℃
Storage humidity: 10~95% (no condensation)
Isolation withstand voltage: 1KVDC between input/output, 1 minute, leakage current 1mA
The RS-485 output and power supply are grounded together.
Surge resistant voltage: 1KVAC, 1.2/50us (peak value)
Dimensions: 106 mm x 59mm x 24mm